Alerts

List alerts changed since a sequence number

Returns alerts whose SequenceNumber is higher than the one sent, deleted ones included (Enabled: false). Send one, and only one, of clientID, facilityID, deviceID or endpointID, and keep the same filter between calls.

get/api/v2/alerts/incremental/{sequenceNumber}

Request

  • Base URL: https://gear.cloud.studio
  • URL: https://gear.cloud.studio/api/v2/alerts/incremental/{sequenceNumber}
  • Auth: one of:
    • HTTP bearer
    • API key in query parameter accessToken

Path parameters

sequenceNumberinteger required

SequenceNumber of the last item received. Use 0 to start from the beginning.

Query parameters

clientIDinteger

Only items of this client.

facilityIDinteger

Only items of this facility.

deviceIDinteger

Only items of this device.

endpointIDinteger

Only items of this endpoint.

maxCountinteger

Maximum number of items in the result.

Response

Alerts changed since sequenceNumber. An empty list means there is nothing new.

AlertIDinteger
VariableTypeIDinteger

Variable the alert watches. User-defined variables are 1000 or higher. Predefined: 1 temperature, 2 humidity, 3 light level, 4 setpoint, 5 volume, 6 active energy, 7 run time, 8 discrete sensor state, 9 dimmerization, 10 weight, 11 flow, 12 voltage, 13 current, 14 active power, 15 reactive power, 16 apparent power, 17 power factor, 18 pressure, 19 frequency, 20 ppm concentration, 21 mass/volume concentration, 22 AQI, 23 people flow, 24 people count, 25 reactive energy, 26 apparent energy, 27 location.

EndpointIDinteger
FacilityIDinteger
ClientIDinteger
ConditionType1 | 2 | 3 | 4 | 5 | 6

1 equal, 2 not equal, 3 greater, 4 greater or equal, 5 lower, 6 lower or equal.

Thresholdnumber double

Value compared with ConditionType to trigger the alert.

NormalConditionType1 | 2 | 3 | 4 | 5 | 6

1 equal, 2 not equal, 3 greater, 4 greater or equal, 5 lower, 6 lower or equal.

NormalThresholdnumber double

Value compared with NormalConditionType to close the alert.

MinimumDurationSecondsinteger

Seconds the condition must hold before the alert triggers.

NotificationEmailsstring[]
NotificationSMSNumbersstring[]
NotificationVoiceNumbersstring[]
Tagsstring[]
SequenceNumberinteger
Enabledboolean

False when the alert was deleted. Deleted alerts only appear in the incremental list.