power
Determine minimum wire gauge using NEC Table 310.16 ampacity ratings with full derating. Looks up base ampacity for copper or aluminum conductors at 60°C, 75°C, or 90°C insulation rating, then applies NEC 310.15(C)(1) ambient temperature correction and NEC 310.15(C)(2) conductor count adjustment. Automatically applies the 125% continuous load factor per NEC 210.20(A) when flagged. Returns the minimum AWG that meets the derated requirement, plus a comparison table of all gauges. Different from wire_gauge which focuses on voltage drop — use both together for complete wire sizing. Essential for residential panels, commercial feeders, solar arrays, and EV charging installations.
post/api/wire_ampacity
Request
- Base URL: https://calc.engineer
- URL: https://calc.engineer/api/wire_ampacity
- Auth: none declared
Request body
Response
Computed result for wire_ampacity
Changes
No recorded changes to this operation across all 1 revision of this API.