title: "Create a new temporary AAR Exception"
method: POST
path: "/temporary-aar-exceptions"
tags: ["Temporary AAR Exceptions"]
---

# Create a new temporary AAR Exception

`POST /temporary-aar-exceptions`

## Request

- Base URL: `https://trolie.example.com`
- URL: `https://trolie.example.com/temporary-aar-exceptions`
- Auth: OAuth 2
  - Client credentials
  - Token URL: `https://no-server/oauth2` scopes: `write:temporary-aar-exceptions`

Create a new temporary AAR Exception

## Request body

- TemporaryAarExceptionRequest: Represents a temporary AAR Exception against a resource. Includes a start and (optional) end time, and a reason. May or may not include a set of values, depending on the business context in which the temporary AAR exception is used.
  - `source` DataProvenance: Provides information about where the associated representation came from. *No functional aspects of the exchange are contingent upon this data.* However, this information is meant to support debugging and application support use cases, so implementors are encouraged to provide meaningful values. * `provider` identifies that entity, e.g., a Ratings Provider or Clearinghouse Provider, that created the object. The `provider`'s NERC id is recommended. * `last-updated` indicates the wall-clock time at the `provider` when the object was last modified. N.b. this is not when the message describing the object was sent or received, i.e., implementors should not simply insert the current timestamp here when preparing the object serialization. * `origin-id` is the identifier used by the `provider` to uniquely nominate the object. It is recommended but not required that this be a URI.
    - `provider` string, required: Contains a unique identifier for an entity, such as a grid operator or organization. This identifier is typically used in the context of data exchange between entities.
    - `last-updated` string, date-time, required: RFC 3339 date-time string with a maximum of 10 digits in the fractional seconds component, i.e., nanosecond precision.
    - `origin-id` string: Contains a identifier that is unique for an object in the context of an exchange between two grid operators.
  - `resource` Names, required
    - `resource-id` unknown, required
    - `alternate-identifiers` object[]
      - `name` string, required: Contains a identifier that is unique for an object in the context of an exchange between two grid operators.
      - `type` string: Type of the name being referenced. Corresponds to the IEC CIM `NameType` concept.
      - `authority` string: Contains a unique identifier for an entity, such as a grid operator or organization. This identifier is typically used in the context of data exchange between entities.
      - `mrid` string: Contains a identifier that is unique for an object in the context of an exchange between two grid operators.
  - `start-time` string, date-time, required: RFC 3339 date-time string with *no fractional seconds component* that designates a start or end to an operating period (such as an hour) that starts at a specified time. This will frequently be at the start of an hour, but may be finer-grained, such as every 30 minutes, should the Clearinghouse Provider choose. If the Transmission Provider is operating in EST, these are valid and equivalent values: * 2023-01-01T06:00Z * 2023-01-01T01:00-5:00 * 2023-01-01T00:00-6:00 * 2023-01-01T11:30+5:30 The server should uniformly represent date-times in the operational time zone of the Clearinghouse Provider.
  - `end-time` string, date-time: RFC 3339 date-time string with *no fractional seconds component* that designates a start or end to an operating period (such as an hour) that starts at a specified time. This will frequently be at the start of an hour, but may be finer-grained, such as every 30 minutes, should the Clearinghouse Provider choose. If the Transmission Provider is operating in EST, these are valid and equivalent values: * 2023-01-01T06:00Z * 2023-01-01T01:00-5:00 * 2023-01-01T00:00-6:00 * 2023-01-01T11:30+5:30 The server should uniformly represent date-times in the operational time zone of the Clearinghouse Provider.
  - `continuous-operating-limit` union, required: Defines the limit. In practice most exchanges will only support one kind of limit for proposals and snapshots. However, the specification supports defining limits on a per resource basis as well as limit types that are not anticipated to be used to implement Order 881. TROLIE server implementations must support at least one of these limit types and should return a well known `application/problem+json` response if they receive a proposal in an unsupported but valid limit type as defined here. When used as the media type parameter `limit-type`, these are nominated by the following names. * `active-power` * `active-power-with-power-factor` * `apparent-power` * `current` * `reactive-power` * `overvoltage-threshold-pu` * `overvoltage-threshold` * `undervoltage-threshold-pu` * `undervoltage-threshold`
    - object
      - `mw` number, float, required: Active Power in megawatts
      - `kV` unknown
    - object
      - `<<` unknown
      - `pf` number, float, required: Assumed power factor.
    - object
      - `mva` number, float, required: Representation of a limit in megavolt-amperes (MVA).
      - `kV` unknown
    - object: Representation of a thermal limit in amperes.
      - `amps` number, float, required
    - object: Representation of a limit in megavolt-amperes reactive (MVAR).
      - `mvar` number, float, required
    - object: An upper limit to voltage for a transmission facility in per unit with the base voltage assumed to be the nominal voltage.
      - `voltage-pu-max` number, float, required
    - object: An upper limit to voltage for a transmission facility in kilovolts.
      - `kV-max` number, required: The voltage in kilovolts.
    - object: An lower limit to voltage for a transmission facility in per unit with the nominal voltage assumed to be the base voltage.
      - `voltage-pu-min` unknown, required
    - object: A lower limit to voltage for a transmission facility in kilovolts.
      - `kV-min` unknown, required
  - `emergency-operating-limits` object[], required: A set of general limit or rating values, each mapped to the various limit bands defined by the Transmission Provider's operating manual. This typically consists of a "normal" limit, as well as limits for various levels of emergency conditions (typically 2-4) defined in the operations manual.
    - `duration-name` string, required: A type of limit as defined in the Transmission Provider's operating manual, usually indicating specific scenarios under which the limit may be used as well as a maximum period for which the limit may be safely applied.
    - `limit` union, required: Defines the limit. In practice most exchanges will only support one kind of limit for proposals and snapshots. However, the specification supports defining limits on a per resource basis as well as limit types that are not anticipated to be used to implement Order 881. TROLIE server implementations must support at least one of these limit types and should return a well known `application/problem+json` response if they receive a proposal in an unsupported but valid limit type as defined here. When used as the media type parameter `limit-type`, these are nominated by the following names. * `active-power` * `active-power-with-power-factor` * `apparent-power` * `current` * `reactive-power` * `overvoltage-threshold-pu` * `overvoltage-threshold` * `undervoltage-threshold-pu` * `undervoltage-threshold`
      - object
        - `mw` number, float, required: Active Power in megawatts
        - `kV` unknown
      - object
        - `<<` unknown
        - `pf` number, float, required: Assumed power factor.
      - object
        - `mva` number, float, required: Representation of a limit in megavolt-amperes (MVA).
        - `kV` unknown
      - object: Representation of a thermal limit in amperes.
        - `amps` number, float, required
      - object: Representation of a limit in megavolt-amperes reactive (MVAR).
        - `mvar` number, float, required
      - object: An upper limit to voltage for a transmission facility in per unit with the base voltage assumed to be the nominal voltage.
        - `voltage-pu-max` number, float, required
      - object: An upper limit to voltage for a transmission facility in kilovolts.
        - `kV-max` number, required: The voltage in kilovolts.
      - object: An lower limit to voltage for a transmission facility in per unit with the nominal voltage assumed to be the base voltage.
        - `voltage-pu-min` unknown, required
      - object: A lower limit to voltage for a transmission facility in kilovolts.
        - `kV-min` unknown, required
    - `limiting-analysis` 'THERMAL_RATING' | 'TRANSIENT_SECURITY_ASSESSMENT' | 'VOLTAGE_SECURITY_ASSESSMENT' | 'SMALL_SIGNAL_STABILITY_ASSESSMENT' | 'SYSTEM_SPECIFIC' | 'ENVIRONMENTAL_CONDITIONS' | 'REGULATORY_REQUIREMENTS' | 'CONTRACT_CAPACITY' | 'OTHER': Indicates how a operating limit was determined. This is used to provide context for the ratings proposals and limits snapshots. When defined in the header, this is assumed to apply to any limit that does not specify its own limiting analysis. When defined for a period, it applies to the `continuous-operating-limit` as well as the associated `emergency-operating-limits`, unless the `emergency-operating-limits` specify their own limiting analysis. THERMAL_RATING - The limit was determined by the thermal rating of underlying equipment. TRANSIENT_SECURITY_ASSESSMENT - Studies of the system's transient stability determined the limit. VOLTAGE_SECURITY_ASSESSMENT - Studies of the system's voltage stability determined the limit. SMALL_SIGNAL_STABILITY_ASSESSMENT - Small-signal stability studies determined the limit. SYSTEM_SPECIFIC - This could account for limits imposed by specific system characteristics, such as the presence of sensitive loads, the need to maintain specific power flows, or other reliability/volatility reasons. These include limits defined by Special Protection Schemes and Remedial Action Schemes. ENVIRONMENTAL_CONDITIONS - The limit was determined by exceptional environmental conditions such as wildfire risk, ice loading, excessive wind/galloping, or other factors. CONTRACT_CAPACITY - The available facility transfer capacity is limited by contractual obligations. REGULATORY_REQUIREMENTS - The limit is imposed by regulatory requirements. OTHER - The limit was determined by some other means not anticipated in this standard.
  - `reason` string, free-form: Free-form text indicating the reason for the exception.

## Response `201`

The temporary AAR Exception was created.

- TemporaryAarException: Data structure for a temporary AAR Exception against a resource. Includes a unique ID, start and (optional) end time, and a reason. May or may not include a set of values, depending on the business context in which the temporary AAR exception is used.
  - `<<` unknown
  - `id` string, required: Contains a identifier that is unique for an object in the context of an exchange between two grid operators.

## Other responses

- `400`: Malformed request
- `401`: Unauthorized
- `403`: Access denied
- `404`: Not Found
- `406`: Not Acceptable (Content negotiation failed)
- `413`: Payload too large
- `415`: Unsupported media type
- `422`: Unprocessable content
- `429`: Too many requests (rate limiting)
- `500`: An unexpected error occurred
- `default`: An unexpected error occurred

## Changes

- **2026-09-23** `92311641b6b2`: 1 info
  - endpoint added

[Operation history](https://skmtc.dev/trolie/apis/transmission-ratings-and-operating-limits-information-exchan/changes/temporary-aar-exceptions/post.md)

---

[API](https://skmtc.dev/trolie/apis/transmission-ratings-and-operating-limits-information-exchan.md) - [All operations](https://skmtc.dev/trolie/apis/transmission-ratings-and-operating-limits-information-exchan/llms.txt) - [OpenAPI document](https://skmtc.dev/trolie/apis/transmission-ratings-and-operating-limits-information-exchan/revisions/92311641b6b2?raw)